DA7000 SERIES A.C. GENERATORS — OPERATION AND PARTS MANUAL — REV. #4 (08/07/09) — PAGE 29
Generator Storage
For storage of the generator for over 30 days, the following
is required:
Drain the fuel tank completely.
Run the engine until
all
the fuel is completely consumed.
Completely drain the oil from the crankcase and refill
with fresh oil.
Disconnect the
negative
battery cable from the battery.
Clean all external parts of the generator with a cloth.
Cover the generating set and store in a clean, dry place.
DA7000SS— MAINTENANCE/PREPARATION FOR LONG -TERM STORAGE
Cleaning the Fuel Filter
Every 100 hours: Clean fuel filter (Figure 21) every 100
hours of operation or once a month to remove dust or water.
1. Place fuel cock lever in the close position.
2. Disconnect fuel lines from fuel filter.
3. Remove the top cap (Figure 22) from the fuel filter and
rinse cap and filter bowl with diesel fuel.
4. Remove element, and rise with diesel fuel.
5. Reinstall fuel filter and connect fuel lines.
Figure 21. Fuel Cock Lever (OFF)
Figure 22. Fuel Filter Disassembly
Radiator
Check Daily: Always check the level of the coolant in the
radiator before starting the engine. Remove the radiator cap
and verify that the coolant reaches top of radiator coils.
1. DO NOT remove the radiator cap while the coolant is
hot. The possibility exists of severe burns or scalding
from the coolant gushing out. Let the coolant
cool
before
removing radiator cap.
2. Check coolant in the reserve tank daily (Figure 23). Make
sure the level is between the FULL (H) and LOW (L)
markings. Fill reserve tank with a mixture of 50/50
antifreeze/water.
Figure 23. Readiator/Reserve Tank
6. Inspect all fuel lines every 50 hours.